FY2009 Water Quality Testing Results

FY2009 Drinking Water Quality Testing Results

It is vital that tap water always be reliable and safe to drink. At our Water Examination Laboratory, we carry out detailed quality testing of water, including raw water from the Yodo River, water at each stage of the purification process in purification plants, and tap water supplied to various parts of Osaka City, every day throughout the year. We also monitor water quality in 40 different locations around the City continuously, 24 hours a day, using automatic remote monitoring devices.
Drinking water tested from April to September 2009 met all requirements, including standard values for Water Quality Standard Items and complementary Water Quality Management Target Items.
Meanwhile, on April 1, 2009, the number of Water Quality Standard Items totaled 50 after 1,1-dichloroethylene was deleted from the list of Water Quality Standard Items (and added to the list of Water Quality Management Target Items) and cis-1,2-dichloroethylene was relisted as “Cis-1,2-dichloroethylene and trans-1,2-dichloroethylene.”

Water Quality Standard Items (50 items)

Item Standard value Drinking water (average value) Water purification plant outlets 1)
1 Standard plate count bacteria Number of colonies formed in 1 ml sample must be 100 or less. 0/ml  
2 E. coli bacteria Must not be detected. Not detected  
3 Cadmium and its compounds 0.01 mg/l or less Less than 0.001 mg/l *
4 Mercury and its compounds 0.0005 mg/l or less Less than 0.00005 mg/l *
5 Selenium and its compounds 0.01 mg/l or less Less than 0.001 mg/l *
6 Lead and its compounds 0.01 mg/l or less Less than 0.001 mg/l  
7 Arsenic and its compounds 0.01 mg/l or less Less than 0.0005 mg/l *
8 Hexavalent chromium compounds 0.05 mg/l or less Less than 0.005 mg/l  
9 Cyanide ion and cyanogen chloride 0.01 mg/l or less Less than 0.001 mg/l  
10 Nitrate nitrogen and nitrite nitrogen 10 mg/l or less 1.1 mg/l  
11 Fluorine and its compounds 0.8 mg/l or less 0.09 mg/l  
12 Boron and its compounds 1.0 mg/l or less 0.02 mg/l *
13 Carbon tetrachloride 0.002 mg/l or less Less than 0.0001 mg/l *
14 1,4-Dioxane 0.05 mg/l or less Less than 0.0005 mg/l *
15 Cis-1,2-dichloroethylene and trans-1,2- dichloroethylene 0.04 mg/l or less Less than 0.0004 mg/l *
16 Dichloromethane 0.02 mg/l or less Less than 0.001 mg/l *
17 Tetrachloroethylene 0.01 mg/l or less Less than 0.0001 mg/l *
18 Trichloroethylene 0.03 mg/l or less Less than 0.0003 mg/l *
19 Benzene 0.01 mg/l or less Less than 0.001 mg/l *
20 Chloric acid Less than 0.6 mg/l 0.034 mg/l  
21 Chloroacetic acid 0.02 mg/l or less Less than 0.002 mg/l  
22 Chloroform 0.06 mg/l or less 0.003 mg/l  
23 Dichloroacetic acid 0.04 mg/l or less Less than 0.001 mg/l  
24 Dibromochloromethane 0.1 mg/l or less 0.006 mg/l  
25 Bromic acid 0.01 mg/l or less 0.0022 mg/l  
26 Total trihalomethanes 2) 0.1 mg/l or less 0.016 mg/l  
27 Trichloroacetic acid 0.2 mg/l or less Less than 0.001 mg/l  
28 Bromodichloromethane 0.03 mg/l or less 0.005 mg/l  
29 Bromoform 0.09 mg/l or less 0.002 mg/l  
30 Formaldehyde 0.08 mg/l or less Less than 0.002 mg/l  
31 Zinc and its compounds 1.0 mg/l or less Less than 0.1 mg/l  
32 Aluminum and its compounds 0.2 mg/l or less 0.01 mg/l  
33 Iron and its compounds 0.3 mg/l or less Less than 0.03 mg/l  
34 Copper and its compounds 1.0 mg/l or less Less than 0.1 mg/l  
35 Sodium and its compounds 200 mg/l or less 21 mg/l  
36 Manganese and its compounds 0.05 mg/l or less Less than 0.001 mg/l  
37 Chloride ion 200 mg/l or less 15 mg/l  
38 Calcium, magnesium etc. (hardness) 300 mg/l or less 44 mg/l *
39 Evaporation residue 500 mg/l or less 115 mg/l *
40 Anionic surfactants 0.2 mg/l or less Less than 0.02 mg/l *
41 Geosmin 0.00001 mg/l or less Less than 0.000001 mg/l  
42 2-Methylisoborneol 0.00001 mg/l or less Less than 0.000001 mg/l  
43 Nonionic surfactants 0.02 mg/l or less Less than 0.005 mg/l *
44 Phenols 0.005mg/l or less Less than 0.0005 mg/l *
45 Organic substances (TOC [total organic carbon] amount) 3 mg/l or less 0.8 mg/l  
46 pH value 5.8 ~ 8.6 7.6  
47 Taste Must not be abnormal. No abnormalities  
48 Odor Must not be abnormal. Chlorine odor  
49 Chromaticity 5 degrees or less 1 degree  
50 Turbidity 2 degrees or less Less than 0.5 degrees  

Water Quality Management Target Items (28 items)   * No items 6 or 11 on the list.

Item Standard value Drinking water (average value) Water purification plant outlets 1)
1 Antimony and its compounds 0.015 mg/l or less 0.00017 mg/l *
2 Uranium and its compounds 0.002 mg/l or less (provisional) Less than 0.0001 mg/l *
3 Nickel and its compounds 0.01 mg/l or less (provisional) Less than 0.001 mg/l *
4 Nitrite nitrogen 0.05 mg/l or less (provisional) Less than 0.02 mg/l  
5 1,2-Dichloroethane 0.004 mg/l or less Less than 0.0001 mg/l *
7 1,1,2-Trichloroethane 0.006 mg/l or less Less than 0.0001 mg/l *
8 Toluene 0.2 mg/l or less Less than 0.006 mg/l *
9 Di (2-ethylhexyl) phthalate 0.1 mg/l or less Less than 0.006 mg/l  *
10 Chlorous acid 3) 0.6 mg/l or less - *
12 Chlorine dioxide 3) 0.6 mg/l or less - *
13 Dichloroacetonitrile 0.01 mg/l or less (provisional) Less than 0.001 mg/l  
14 Chloral hydrate 0.02 mg/l or less (provisional) Less than 0.001 mg/l  
15 Agricultural chemicals 4) Sum of ratios of detected values to guideline values of all individual agricultural chemicals should be 1 or less. 0.00 *
16 Residual chlorine 1 mg/l or less 0.4 mg/l  
17 Calcium, magnesium, etc. (hardness) 10 mg/l or above, and 100 mg/l or less 44 mg/l * 
18 Manganese and its compounds 0.01 mg/l or less Less than 0.001 mg/l  
19 Free carbon dioxide 20 mg/l or less 2.5 mg/l *
20 1,1,1-Trichloroethane 0.3 mg/l or less Less than 0.003 mg/l *
21 Methyl tert-butyl ether (MTBE) 0.02 mg/l or less Less than 0.0002 mg/l *
22 Organic substances, etc. (potassium permanganate consumed) 3 mg/l or less 1.1 mg/l *
23 Threshold odor number (TON) 3 or less 1 *
24 Evaporation residue 30 mg/l or above, and 200 mg/l or less 115 mg/l *
25 Turbidity 1 degree or less Less than 0.5 degrees  
26 pH value Approx. 7.5 7.6  
27 Corrosivity (Langelier index) Should be approx. -1 or above, and as close to 0 as possible. -1.2 *
28 Heterotrophic bacteria Number of colonies formed in 1 ml sample must be 2,000 or less. (provisional) 2/ml  
29 1,1-Dichloroethylene 0.02 mg/l or less Less than 0.001mg/l *
30 Aluminum and its compounds 0.1 mg/l or less 0.01 mg/l  

 

  1. Values with * in the rightmost columns were measured at water purification plant outlets; other values were measured at water faucets in 21 locations around the City.  
  2. Total trihalomethanes are the sum of the concentrations of chloroform, dibromochloromethane, bromodichloromethane and bromoform.
  3. Chlorous acid and chlorine dioxide were not measured because chlorine dioxide is not used in the water purification process.
  4. In Osaka City, the levels of 99 different agricultural chemicals are measured, and a guideline value is set for each agricultural chemical. A target value for “Agricultural chemicals” is set for the sum of the ratios of detected values to the guideline values of all individual agricultural chemicals.

 

List of agricultural chemicals (Japanese only)

It is a document of Adobe Co. PDF form.  List of agricultural chemicals (pdf, 82.80KB)

 

[Page FY2006 Water Quality Testing Results under Industrial Waterworks under FY2005 Water Quality Testing Results on the Osaka City Waterworks Bureau Website ends here.]

Pure Water Clear Future Osaka City Waterworks Bureau supplies water purified by advanced water
treatment to all areas of the city.

Handling of Personal InformationCopyrightsLinking to the Osaka City WebsiteDisclaimerHow to Use this Site

World Trade Center Building (WTC), 1-14-16 Nanko-kita, Suminoe-ku, Osaka, Japan, 530-8201
TEL: +81-6-6458-1132 FAX: +81-6-6458-2100

Copyright(c) Osaka city waterworks bureau All rights reserved